The EA-040-A10 can install a maximum of 40 air intakes.
(Analog, maximum air intake 40pcs x 100m, maximum tube length is 4,000m)
Ambient temperature: 0~390C
Humidity: 10~95%
Voltage: DC 24V
Pipeline straight: 40x100m
Tube size: Outside 6mm, inside 4mm / outside 4mm, inside 2.5mm
Induction form: Smoke is drawn into the holes and moved into a chamber, where scattered light technology detects the presence of smoke
Range: 0.025~20.0% obs/m
Color: Silver
Dimensions: 352(W) x 336(H) x 135.5(D)mm
IP: 40
Weight: 10kg
Relay : 7 programs
VEA can determine the exact location of the fire, so it is suitable for offices, hospitals, schools, prisons, high-rise buildings, information storage areas and warehouses.
Address: No. 3, Street 40, An Phu Hung Residential Area, Neighborhood 5, Tan Phong Ward, District 7, Ho Chi Minh City
Tel: 028 5433 3313 - 0934 308 475 (Korea) - 0931 788 132 (VN)
Email: dncvina@dncvina.com Web: www.dncvina.com